8. DISCONNECTING FROM VOLTAGE SOURCES
Before proceeding any operations on inverter, please disconnect the
inverter from all voltage resources as described in this manual.
Following these steps in described sequence are mandatory.
1.
Disconnect miniature circuit-breaker and prevent from unintentional
reconnections.
2.
Open the DC switch and prevent the switch from closing
unintentionally.
3.
Use clamps to ensure there is no electrical current in DC wires.
4.
Disconnect all DC connections and resources. Unplug the DC
connectors, and DO NOT pull the cables.
5.
Use multimeter to ensure the voltage on DC terminals of inverter is 0.
6.
Unscrew and remove the AC connector.
Danger to life due to high voltages.
Inverter capacitors need 5 minutes to be completely de-
energized. When an error occurs, DO NOT remove the cover of the
inverter onsite. Improper operations and attempts may induce
electric shock.
18
9. TECHNICAL PARAMETERS
Module
Max. PV Power (Wp)
Max Input Voltage (V)
MPP Voltage Range (V)
Min DC Voltage (V)
Nominal DC-input
Voltage (V)
Max. Input Current (A)
Max. Short DC current (A)
No. Of independent
MPPT inputs
No. Of PV strings
per MPPT
Max inverter backfeed
current to the array (A)
Rated Power (W)
Max. Apparent AC
power (VA)
Rated grid voltage (Vac)
Rated power frequency (Hz)
Max output current (A)
Max output overcurrent
protection (A)
Inrush current (Peak and
duration)*
Max. output fault current
(Peak and duration)*
Adjustable displacement
power factor
V.2
EINSOLAR25Y
15Y
EINSOLAR
INPUT/DC
22500
30000
1000
200-900
150
620
13 per string
20 per string
2
2
0
OUTPUT/AC
15000
25000
16500
25000
380/400
50/60
24
36.3
50
40
18.4A@
18.4A@
0.214ms
0.214ms
35.5A
35.5A
@420us
@420us
0.8ind a
0.8cap
19
V.2