Information on grounding components:
Object
Description
1
Housing
2
M5 terminal lug with protective conductor
3
M5×13 pan head screw
5. COMMISSIONING

5.1 Safety Instructions

1.
Measure the frequency and voltage of grid connection and make sure
they follow the inverter's grid connection specifications.
2.
An external circuit-breaker on the AC side (or a fuse) at 1.25*AC rated
current is strongly recommended.
3.
Reliability of all earth connections must be tested and valid.
4.
Before commissioning, disconnect the inverter and the circuit-breaker
or fuse, and prevent accidental reconnection.
10
5.2 AC Wire Assembly and Connection
5.2.1
AC Commissioning
Approx. 60mm
For "L1" , "L2","L3"and "N"
Unscrew the swivel nut from
the threaded sleeve,
then thread the swivel nut and
threaded sleeve over
the AC cable
5.2.2 AC Switch Types
Please install an individual 2-stage miniature circuit breaker according
to the following specifications.
Model
EINSOLAR5Y
EINSOLAR10Y
V.2
Step 1
N
PE
7-9mm
4....6mm²
1
L
Approx. 65mm
2
Insert the conductor into a suitable ferrule
acc. to DIN 46228-4 and crimp.
Assemble the locking cap,
Insert the crimped conductors, L, N and PE
threaded sleeve and swivel
into corresponding terminals and tighten
nut together.
the screws (torque 0.6±0.1N·m).
Maximum output
current (A)
8.5
15.2
11
Step 2
Step 3
1
2
Screw the AC connector and
tighten firmly into socket.
AC Breaker Rated
current(A)
16
25
V.2