Safety Instructions - EAS ELECTRIC EINSOLAR36Y Manual De Usuario E Instalacion

Ocultar thumbs Ver también para EINSOLAR36Y:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1
2
3
Information on grounding components:
Object
Description
Housing
1
2
Terminal lug with protective conductor
3
M6×16 screw SUS304
PE Conductor cross-section: 16mm²
AC Cable Cross-section
PE Cable Cross-section
16<S≤35mm2
16mm2
S>35mm2
Cable Specifications
Type
No
Item
Single-core outdoor copper
1
PE cable
cable
2
AC Output
Outdoor copper
cable
cable
3
DC Input
Standard outdoor PV cable,
cable
PV1-F Model recommended
4
Meter/
Two-core outdoor shielded
DRED
twisted pair cable
Note
Only suitable when the material of
PE cable is aligned with other AC
phase cables. In case the materials
are different, please ensure the
resistance is equivalent to the
S/2
figure mentioned in the table.
Specifications
Conductor cross-section: ≥ 16mm²
Conductor cross-section: L/PE: 16mm²
Cable outer diameter: 21-51 mm
Conductor cross-section: 4-6 mm²
Cable outer diameter: 5-8 mm
Conductor cross-section: 0.14-1.5 mm²
Cable outer diameter: approx. 4-6 mm
10
5. COMMISSIONING

5.1 Safety Instructions

1.
Measure the frequency and voltage of grid connection and make sure
they follow the inverter's grid connection specifications.
2.
An external circuit-breaker on the AC side (or a fuse) at 1.25*AC rated
current is strongly recommended.
3.
Reliability of all earth connections must be tested and valid.
4.
Before commissioning, disconnect the inverter and the circuit-breaker
or fuse, and prevent accidental reconnection.
5.2 AC Wire Assembly and Connection
5.2.1
AC Commissioning
5.2.2 AC Switch Types
Please install an individual 2-stage miniature circuit breaker according
to the following specifications.
Model
EINSOLAR36Y
N: 6mm²
EINSOLAR50Y
V.2
Maximum output
AC Breaker Rated
current (A)
current(A)
60
80
100
80
11
V.2

Publicidad

Tabla de contenido
loading