Safety Instructions; Cable Specification - EAS ELECTRIC EINSOLAR5V Manual De Usuario E Instalacion

Ocultar thumbs Ver también para EINSOLAR5V:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1
2
3
Information on grounding components:
Object
Description
1
Housing
2
M5 terminal lug with protective conductor
3
M5×13 pan head screw
PE Conductor cross-section: 6mm²

4.5 Cable Specification

Cable specifications
Item
Type
1
PE Cable
Single-core outdoor
copper cable
Outdoor copper
2
AC Output
cable
cable
3
DC Input
Standard outdoor PV
cable, PV1-F Model
cable
recommended
4
Meter
Two-core outdoor
shielded twisted
pair cable
5
DRED
CAT-5E, outdoor shielded
cable
Standard for EIA/TIA 568B
Specifications
 Conductor cross-section: 6mm2
 Cross-section: 4-6mm2
 Cable outer diameter: 9-14mm
 Conductor cross-section:
2.5-6mm2
 Cable outer diameter: 5-8mm
 Conductor cross section:
0.14-1.5mm2
 Cable outer diameter: approx 9mm
 Cable outer diameter: approx.
9mm
 Cable maximum length: 1000m
10
5. COMMISSIONING

5.1 Safety Instructions

1.
Measure the frequency and voltage of grid connection and make sure
they follow the inverter's grid connection specifications.
2.
An external circuit-breaker on the AC side (or a fuse) at 1.25*AC rated
current is strongly recommended.
3.
Reliability of all earth connections must be tested and valid.
4.
Before commissioning, disconnect the inverter and the circuit-breaker
or fuse, and prevent accidental reconnection.
5.2 AC Wire Assembly and Connection
5.2.1
AC Commissioning
Approx. 45 mm
For "L" and "N"
Insert the conductor into a
suitable ferrule acc. to DIN 46228-4 and
crimp
5.2.2 AC Switch Types
Please install an individual 2-stage miniature circuit breaker according
to the following specifications.
Model
EINSOLAR5V
EINSOLAR6.5V
V.2
Step 1
Approx. 10 mm
4....6mm²
L
N
Approx. 50mm
PE
For "PE"
Assemble the locking cap,
Insert the crimped conductors L, N and
threaded sleeve and swivel
PE into corresponding terminals and tighten
nut together
the screws (torque 1.4N·m)
Note: Please insure that the connector has been correctly installed!
Maximum output
current (A)
23
29.6
11
Step 2
Step 3
1
2
Screw the AC connector
firmly into the socket
AC Breaker Rated
current(A)
32
40
V.2