Connecting the batteries

The nBox can either be equipped with a set of batteries comprising 2 series-connected lead-acid gel batteries
(2 × 12 V) or a single lithium iron phosphate battery (24 V).
·
With the nBox S, batteries with a capacity of 10 Ah or 12 Ah can be used.
The nominal voltage of the set of batteries is 24 V DC.
WARNING
Danger of chemical burns from electrolyte!
This system uses batteries containing sulphuric acid electrolyte. Sulphuric acid causes severe
chemical burns on the skin and eyes.
w
Batteries can only be installed by authorised personnel wearing appropriate protective clothing.
w
Batteries cannot be drilled into or otherwise damaged.
w
In case of skin contact with electrolyte: rinse the affected area immediately with water.
Attention
Impaired performance and safety of the system.
w
Other batteries not prescribed here must not be used.
w
Vehicle starter batteries must not be used.
w
In the case of centrally supplied emergency lighting systems, batteries with a proven service life of
at least ten years must be used at an ambient temperature of 20°C.
w
Batteries must be set up and maintained in accordance with EN 50272-2 and the battery
manufacturer's recommendations must be followed.