Ip Connection, Communication And Control Module - Optimus IF-702ETH Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.1. IP Connection, communication and control module

1)
Ground connection
2)
FUSE. 2.5 A Secondary power supply fuse.
3)
POWER SUPPLY 2
24 VDC Secondary power input.
4)
GND Contact
5)
FAIL Contacts
Fail relay. Switches when a system alarm is detected.
Maximum DC charge current: 150 mA
Maximum DC or AC peak charge voltage: 350 V
6)
BUS
CAN Contacts
Data communication bus between the IF-702ETH and
the system peripherals (MD-30C, ME-200C, NS-CAN).
7)
OUTPUT CT Contacts
Incorporates three output contacts configured as dry
contacts. Each contact has two terminals (A and B).
The functionality and stand-by state (NC/NO) are
configured through the Call Point software. They may be
configured as general purpose contacts or in the
evacuation system as fault notification contacts,
Emergency Mode indicator activated...
IF-702ETH version 5.0.001
IF-702ETH
Figure 3
8)
INPUT Contacts CT 1, 2 and 3
Incorporates three input contacts.
The functionality and stand-by state (NC/NO) are
configured through the Call Point software. They may be
configured as general purpose contacts or in the
evacuation system as emergency mode activation
contacts, evacuation message activated...
The detection time of the activation pulse of the input
contacts is configurable through the Call Point software
(0-50-100-200-300-400-500-1000-1500-2000
milliseconds).
If you wish, the system may monitor these contacts
(short-circuit or open line detection).
9)
ETH B Connector
Is used in a redundant network as a secondary
connection to the IP network.
10) ETH A Connector
Is used to connect the unit to the IP network.
11) LINK/ACTIVITY indicator (green LED):
When illuminated it indicates a network connection.
When flashing it indicates that data is being sent or
received.
12) SPEED indicator (yellow LED):
Speed of the network. If the LED is lit, indicates a speed
of 100 Mbps. If unlit, indicates a network speed of 10
Mbps (it is highly recommended to use a transmission
speed of 100 Mbps).
R+D Department
IP Audio interface
2 outputs
6

Publicidad

Tabla de contenido
loading

Tabla de contenido