Romus D-20L Manual De Instrucciones página 31

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

components, the casing is not altered in such a way that the level of protection is affected.
· This shall include damage to cables, excessive number of connections, terminals not
made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that
apparatus is mounted securely. Ensure that seals or sealing materials have not degraded
such that they no longer serve the purpose of preventing the ingress of flammable
atmospheres.
Replacement parts shall be in accordance with the manufacturer's specifications.
· NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior to
working on them.
REPAIR TO INTRINSICALLY SAFE COMPONENTS
· Do not apply any permanent inductive or capacitance loads to the circuit without ensuring
that this will not exceed the permissible voltage and current permitted for the equipment
in use. Intrinsically safe components are the only types that can be worked on while live in
the presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result
in the ignition of refrigerant in the atmosphere from a leak.
CABLING
· Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. The check shall also take into
account the effects of aging or continual vibration from sources such as compressors or
fans.
DETECTION OF FLAMMABLE REFRIGERANTS
· Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used.
LEAK DETECTION METHODS
· The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants. Electronic leak detectors shall be used to detect flammable
refrigerants, but the sensitivity may not be adequate, or may need recalibration. (Detection
equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not
a potential source of ignition and is suitable for the refrigerant used. Leak detection
equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated
to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is
confirmed. Leak detection fluids are suitable for use with most refrigerants but the use
of detergents containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall
www.romusworld.com
www.romusworld.com
194407
EN
29

Publicidad

Tabla de contenido
loading

Productos relacionados para Romus D-20L

Este manual también es adecuado para:

194407

Tabla de contenido