Tecsis P3298 Manual De Instrucciones página 27

Ocultar thumbs Ver también para P3298:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6. Commissioning, operation
Fitting the DIN 175301-803 A angular connector
1. Loosen the screw .
2. Loosen the cable gland .
3. Pull the angled socket  +  from the
instrument.
4. Via the mounting hole , lever the
terminal block  out of the case .
5. Pass the cable with the appropriate cable outer
diameter through the cable gland , ring ,
sealing  and the case .
6. Connect the cable ends to the connection termi-
nals on the terminal block  in accordance with
the pin assignment (see "Connection diagrams"
for the pin assignment).
7. Press the terminal block  into the case .
8. Tighten the cable gland  around the cable.
Make sure that the cable gland and seal are not
damaged and that they are assembled correctly
in order to ensure ingress protection.
9. Place the flat, square gasket  over the pressure
sensor's connection pins.
10. Slide the assembled angled socket  +  onto
the pressure sensor's connection pins.
11. Using the screw , screw the angled socket to the
pressure sensor, hand-tight.
Operating instructions Pressure sensor, P3298
 Mounting hole
GB
27

Publicidad

Tabla de contenido
loading

Tabla de contenido