INSTALLATION INSTRUCTIONS
Step 3 - Installation of the Outdoor Unit (Cont.)
Model Number
Factory
Charge
Unit
oz
2U18MS2HDA
60
3U24MS2HDA
67
4U36MS2HDA
90
2U20EH2HDA
69
3U24EH2HDA
82
4U36EH2HDA
102
5U42MS2HDA
113
D. Install Copper Lineset
• Line set sizes are determined by the indoor unit. See indoor spec for information. The outdoor unit ships with port
adapters to reduce or enlarge the flare port sizes when needed. If connecting to 24K models with 3/8" & 5/8" ports,
adapters must be ordered separately.
• Cut the line set to length.
• Place nut over the pipe and then flare with the R-410A flaring tool.
NOTE: Follow standard practices for creating pipe flares. When cutting and reaming the tubing, use caution to prevent
dirt or debris from entering the tubing. Remember to place nut over the tubing before flaring.
• To join the line set, directly align the tubing flare to the fitting on the other pipe. Slide the nut onto the fitting and hand
tighten.
• Torque the fittings according to the specifications shown in the torque chart below.
• Two wrenches are required to join the flare connection; one standard wrench and one torque wrench
adjusted to the proper settings.
• Repeat the process for attaching the other end of the line set.
CAUTION
Indoor Unit
Outdoor Unit
itioned
24
Refrigerant Charge and Pipe Length Information
Total Pipe
Additional
Length of
charge rule
factory charge
ft
oz/ft
50
100
131
66
0.2
100
131
164
Forced fastening without careful centering will
damage the threads and cause a refrigerant leak.
Pipe Diameter (ø)
1/4"
3/8"
1/2"
5/8"
Outdoor Unit
)
Indoor Unit
If the outdoor unit is
than one or more indoor units.
(If lower than one or more indoor units.)
Branch
System
Maximum
Maximum
pipe length
pipe length
ft
ft
65
98
82
197
82
230
82
165
82
197
82
230
82
262
Fastening torque
18N.m/13.3Ft.lbs
42N.m/30.1Ft.lbs
55N.m/40.6Ft.lbs
60 N.m/44.3Ft.lbs
If all indoor unit are
the outdoor units.
Minimum pipe length
ft
10' per indoor
Half union
Flare nut
Spanner
Torque wrench
e el
di