INSTALLATION INSTRUCTIONS
Outdoor Unit Clearances
NOTE: Fix the unit by inserting bolts, wire or other foundation options if there is danger that the unit will fall or turn over.
NOTE: Place the unit on a level mounting base (or a plastic pedestal) for proper drainage.
NOTE: Install the outdoor unit in a level position. Failure to do so may result in water leakage or accumulation.
NOTE: Heat pump models will generate condensate water on the outdoor unit. Stacking the units without managing
condensate water may create failure on the lower unit.
(3) Installation and maintenance space
Selection of installation location of outdoor
Above
12(300)
Above 40(1000)
Select the Outdoor location:
• Choose a level place solid enough to bear the weight
and vibration of the OD unit and where the operation
noise will not be amplified.
• Choose a location where the hot air discharge and/or
noise will not create a nuisance for neighbors.
• Ensure there is sufficient space to maneuver the OD
unit into place.
• Ensure there is sufficient space and no obstructions for
the air inlet and outlet.
31-5000564 Rev. 3
Step 1 - Preparation
Above
Above
Above
16(400)
16(400)
16(400)
Above 80(2000)
Above
Above 177(4500)
If wall is half the height of the unit, 8 (250).
If wall is between half the height of the unit and
24(600)
the same height of the unit, 12 (300)
Above16(400)
Above16(400)
Corner
Above
20(500)
• I nstall the unit's power/communication wiring at least
10 feet away from television and radio sets to prevent
interference.
• Ensure any moisture sensitive items are kept away from
the condensate drain path of the OD unit.
• Choose a location not affected by heavy snowfall or
wind.
• Install a wind baffle to prevent wind exposure.
15