The appliance must not be located neither directly below, nor in
•
front of a socket-outlet.
The heater must be installed so as to prevent that the switches can
•
be touched from those who are in the shower.
Ensure that there is no possibility of inflammable material, com-
•
bustible material or curtains coming into contact with the heater,
or lie near the heater.
The product is in class I and IP55, wich is the protection rate for
•
the units to be used even outdoor. For keeping the protection rate
of the appliance, the connection of the appliance with the power
supply must be done by means of a minimum IP55 system, as per
the standards HD 384 CENELEC for Europe, or international IEC
60346-7-708 1988.
3. FITTING
Before being used, the heater must be fixed to the wall or to
the ceiling by means of the provided supports, as described
below. Before drilling the holes for the dowels, be sure that
the wall is solid and that you are far from water tubes or electrical
wires. Be sure that the heater is not facing the ceiling or inflammable
materials.
1. Drill four holes in the wall, following the dimensions in the table
below:
7715
800 (**)
104 (*)
Hole spacing (mm)
The value of wheelbase 104 (*)
must be respected, while those
relating to the distance between
the sliding brakets (**) are only
recommended.
7718
950 (**)
104 (*)
7724
1300 (**)
104 (*)
9
7732
1600 (**)
104 (*)