Comms + and – from the control panel. Otherwise use
AUX PWR from DGP's or an auxiliary power supply.
The RAS is connected to the ATS panel via the RS485 data
bus, up to 1.5 km from the control panel. It is recommended to
use two-pair twisted, shielded data cable (WCAT 52/54). The
shield of any bus cable must be connected to system ground at
one end only. The ATS115x RAS does not provide an earth
connection for this purpose. If the bus is daisy-chained to the
RAS, ensure that the shield of the cable is jointed to provide
continuity of data cable shield. Isolate the wires and the shield
of the cable correctly to prevent any short circuit on the
keypad.
Links
•
TERM: Fitted if this device is the last device on the system
databus. For more details see the ATS control panel
installation guide.
LEDS
See Figure 8.
•
L1: Dual-colour LED red or green. Green when an area is
disarmed (area assigned to the RAS alarm group). Red
when an area is armed (area assigned to the RAS alarm
group).
If area is disarmed and the door is opened, it flashes
green for the access time. If area is armed, and the door is
opened, it flashes red for the access time.
Note:
This LED stays off when no areas are assigned to
its alarm group.
•
L2: Yellow LED. Yellow is the "ready" LED. When the area
is ready to set, the yellow LED is on. All the inputs in the
area assigned to the RAS alarm group should be sealed.
•
L3: Red LED. Red and flashing when an alarm occurs in
any of the areas assigned to the RAS.
Specifications
Supply voltage
Current consumption
Open collector output ("OUT" terminal)
ACE type (tamper protection)
Dimensions (H x W x D):
ATS1151
ATS1156
Operating temperature
Relative humidity
IP rating
Weight:
ATS1151
ATS1156
4 / 24
8.5 to 14.0 V
45 mA at 12 V
15 V max. at 50 mA max.
B
96 x 67 x 28 mm
96 x 96 x 40 mm
−25 to +70°C
< 95% noncondensing
IP43
226 g
458 g
Regulatory information
Manufacturer
PLACED ON THE MARKET BY:
Carrier Fire & Security Americas Corporation Inc.
13995 Pasteur Blvd
Palm Beach Gardens, FL 33418, USA
AUTHORIZED EU REPRESENTATIVE:
Carrier Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Product warnings
THESE PRODUCTS ARE INTENDED FOR SALE
and disclaimers
TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS. CARRIER FIRE &
SECURITY CANNOT PROVIDE ANY
ASSURANCE THAT ANY PERSON OR ENTITY
BUYING ITS PRODUCTS, INCLUDING ANY
"AUTHORIZED DEALER" OR "AUTHORIZED
RESELLER", IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE
AND SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and
product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/
Certification
EN 50131
ATS1151 variant only.
EN 50131-1 System requirements
EN 50131-3 Control and indicating equipment
Security Grade 3, Environmental class III
Tested and certified by VdS Schadenverhütung
GmbH.
Carrier Fire & Security hereby declares that this
device is in compliance with the applicable
requirements and provisions of the Directive
2014/30/EU and/or 2014/35/EU. For more
information see www.firesecurityproducts.com or
www.aritech.com.
REACH
Product may contain substances that are also
Candidate List substances in a concentration
above 0.1% w/w, per the most recently published
Candidate List found at ECHA Web site.
Safe use information can be found at
https://firesecurityproducts.com/en/content/intrusi
on-intro
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info
Contact information
www.firesecurityproducts.com or www.aritech.com
For customer support, see www.firesecurityproducts.com
DA: Installations vejledning
Montering af enheden
Fjern unbrakoskruerne fra monteringspladen til læseren
1.
for at åbne læseren (figur 5).
P/N 466-2512 (ML) • REV D • ISS 10DEC20
or scan the QR code.