FONESTAR ZS-2000M Manual De Instrucciones página 8

Central megafonía y alarma por voz en 54
Ocultar thumbs Ver también para ZS-2000M:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
The ZS-2000M supports manually or automatically starting fire emergency voice alarm. The priority level of
manual operation is higher than that of automatic broadcasting.
Manual operation includes selecting broadcasting zones and starting or stopping emergency broadcasts.
Operators can perform emergency voice broadcasting through the PTT microphone (Optional). The ZS-
2000M can automatically record up to 30 minutes of paging content.
When the PTT microphone is used to perform emergency paging, fault prompt tones and monitoring pauses
and the system returns to its original working state within 3 seconds after the completion of broadcasting.
PUBLIC ADDRESS FUNCTION
The ZS-2000M has the following common public address functions:
- Supports broadcasting multiple sound sources (external input sources, background music, recorded
voice sound files, and microphone sources) in multiple zones.
- Automatically broadcasts locally stored recorded voice sound files, network audio, and background
music.
- Automatic timed broadcasting and timer data are uploaded to the equipment after being set through the
software.
- Dry contacts trigger specified broadcasting, and events triggered by the dry contacts can be configured
through the software as well as automatically perform preconfigured task when receiving dry contact
signals.
- Can broadcast audio based on the signals sent from the dry contacts and serial data.
PAGING FUNCTION
Selected ZS-2000M zones can receive paged broadcasts. A configured pre-signal can be played first to alert
users of an incoming paging session. Users can then communicate with each using the ZS-200M.
SOFTWARE CONFIGURATION FUNCTION
The following ZS-2000M features can be configured through the software:
- Number of zones (1-8)
- Loudspeaker circuit impedance detection
- Sound file playlist
- Broadcast operations (including sound sources, play modes, audition, priority levels, and related
operations)
- AVC function
- Network monitoring function
- Equipment ID and IP address
- Power amplifier
- Main and standby power amplifier detection and switching
- Uploaded recorded voice sound files
- Pre-signal (except PTT microphone)
- Dry contact input trigger broadcasting
- Emergency broadcasting
- Various fault detection functions
- Timer broadcasting
- Dry contact output function
Configuration data is uploaded to the ZS-2000M through the network, and the ZS-2000M system
automatically reboots so as to allow the configured data to take effect.