IP protection types;
•
Installation of electrical installation material;
•
Type of supply network (TN system, IT system, TT system) and
the resulting connecting conditions (classical zero balancing,
protective earthing, required additional measures etc.).
Please observe the hazard information in section see „2 Hazard infor-
mation" on page 28 during installation.
Please note the insulation stripping length of the conductor to be
connected, indicated on the device.
Permitted cable cross-sections for connection to the universal actuator
for 230 V lines are:
Rigid cable [mm
1.5-2.5
Permitted cable cross-sections for connection to the universal actuator
for 0/1–10 V lines are:
Rigid cable [mm
0.25-1.5
5.2
Mounting and installation
Please read this entire section before starting to install the device.
The universal actuator must only be installed by an electrician!
The load circuit must be protected by a circuit breaker in accord-
ance with EN60898-1 (tripping characteristic B or C, max. 16 A rated
current, min. 6 kA breaking capacity, energy limitation class 3).
Make sure that no electricity or similar lines run at the desired
mounting location!
]
Flexible cable without ferrule [mm
2
1.5-2.5
]
Flexible cable without ferrule [mm
2
0.25-1.5