INSTALLATION
The floor of the room where the stove will be installed must be of size
and structure sufficient to support its weight.
If an existing construction does not meet this prerequisite, adequate
measures (for example, the installation of a load distribution plate) must
be taken to allow the ground to support the device.
In the presence of a wooden floor, provide a protective surface in accor-
dance with the regulations in force in the country.
The wall must be made up of incumbustible materials.
Maintain a minimum rear distance of 20 cm, a lateral distance of 40
cm and a front distance of 100 cm, any wall and any fuel object. These
distances must be respected to allow the technician to carry out main-
tenance, and for the safety of the product itself. In the presence of par-
ticularly delicate objects such as furniture, curtains, sofas, considerably
increase the distance from the stove.
For proper functioning and good distribution of the temperature, the
stove must be placed in a place where the necessary air can circulate for
the combustion of the pellets (about 40 m3/h must be available accor-
ding to the installation standard and according to the regulations in
force in the country). The volume of the environment should not be less
than 20 m3.
It is mandatory to provide an external air intake which allows the com-
bustion air supply necessary for the proper functioning of the stove.
It is recommended to connect the air necessary for combustion directly
to the external air inlet, with a Ø 40 mm hose, with a maximum length of
2 linear meters, each curve of the pipe is equivalent to a leak of a linear
meter (diagram opposite).
It is possible to take the air directly in the room where the stove is
installed, in this case, the air intake of the room must have a total net
minimum surface of 100 cm² protected by an external grid which should
not be obstructed and must be cleaned periodically. The surface must
be increased accordingly if there are other active generators inside the
room (for example: electric fan for stammering air, hood, other stoves,
etc.) , which can depress the environment.
The air inlet grids must be positioned so that they cannot block or close
accidentally.
CHIMNEY
• The indications below are intended to give information on the construction of a good chimney, but it must in no case be considered
as a substitute for the standards in force in the country of installation, standards of which the qualified manufacturer must be in
possession. The manufacturer of the stove declines any civil or criminal liability concerning the dysfunction of the stove due to a poor
-sized chimney and/or not in accordance with the regulations in force which must be respected.
• The chimney must be built according to manufacturing standards (≥ T200), must be vertical without bottlenecks, must be resistant
to condensation and must be resistant to soot fire. It must be isolated from the outside to avoid cooling of smoke and must be
equipped with a condensate drain. If the chimney is a concrete cavity, it must be tubed.
• The chimney must be able to be inspected for cleaning and must be spaced flammable and/or combustible materials.
• The chimney must always be clean, any residue of soot reduces the section of the fireplace, compromises the draw, and can generate
a hole fire. Clean up the smoke duct and the chimney by a specialized sweater at least once a year and before lighting the stove after
> 40cm
> 100cm
56
> 150cm
> 20cm
> 100cm²