Before installing the oven have a qualified electrician verify
that your home is provided with adequate electrical service
and that the addition of the oven will not overload the
branch circuit on which it is to be installed.
Be sure your appliance is properly installed and grounded
by a qualified technician. Ask your dealer to recommend a
qualified technician or an authorized repair service.
This appliance is manufactured with a green GROUND
wire connected to the oven chassis Junction Box or Wall
Receptacle Location.
Suggested location of the junction box or wall receptacle is
showed in "Cutout requirements" Figure.
LOCATION OF RATING PLATE
NOTE: Alternatively, the rating label can be placed in the
upper corner of the right wall of the enclosure.
Your local codes and ordinances, of course, take precedence
over these instructions. Complete electrical connections
according to local codes and ordinances.
A UL listed conduit connector must be provided at each end
of the power supply conduit (at the range and at the junction
box).
• Wire sizes and connections must conform with the rating
of the range.
In the United States:
Be sure that the electrical and grounding connections and
also wire size are adequate and in conformance with the
National
Electrical Code, ANSI/ NFPA 70-latest edition and all local
codes and ordinances.
In Canada:
Be sure that the electrical connection and wire size are
adequate and in conformance with CSA Standard C22.1,
Canadian Electrical Code, Part 1 - latest edition, and all
local codes and ordinances.
5 - Electrical supply
WARNING
Risk of Electric Shock, frame grounded to neutral of
appliance through a link
Grounding through the neutral conductor is prohibited for
new branch-circuit installations (1996 NEC); mobile homes;
and recreational vehicles, or in an area where local codes
prohibit grounding through the neutral conductor. For
installations where grounding through the neutral conductor
is prohibited:
- Disconnect the ground from the neutral at free end of
conduit;
- Use grounding terminal or lead to ground unit; and
- Connect neutral terminal or lead to branch circuit neutral
in usual manner.
A 3-wire or 4-wire single phase 120/240 or 120/208 Volt,
60 Hz AC only electrical supply is required on a separate
circuit fused on both sides of the line (time-delay fuse or
circuit breaker is recommended). DO NOT fuse neutral.
NOTE: FOR USE WITH 208 V, 60 HZ SUPPLY VOLTAGE,
SEE CONNECTING TO 208 VOLT CIRCUIT.
ELECTRICAL REQUIREMENTS 30"
Electrical Supply
120-240V or 120-208V, 60 Hz
Service
50 amp dedicated circuit
Max Connected Load
120/240V 11.00
120/208V 10.00
Min Supply Wire
L1, L2, ground
Neutral
ELECTRICAL REQUIREMENTS 36" *
Electrical Supply
120-240V or 120-208V, 60 Hz
Service
50 amp dedicated circuit
Max Connected Load
120/240V 14.60 kW
120/208V 13.30 kW
Min Supply Wire
L1, L2, ground
Neutral
ELECTRICAL REQUIREMENTS 48" *
Electrical Supply
120-240V or 120-208V, 60 Hz
Service
50 amp dedicated circuit
Max Connected Load
120/240V 20.30 kW
120/208V 17.60 kW
Min Supply Wire
L1, L2, ground
Neutral
(*) 36" - 48" model utilizes power management software
that maintains maximum load below 50 Amps
EN
kW
kW
10 AWG
12 AWG
10 AWG
10 AWG
8 AWG
10 AWG
11