To carry out the installation with alternating current (230V), the appliance must be connected to the mains
through the plug supplied with the appliance. Therefore, the only operation to be carried out, from the electrical
point of view, will be the connection of this cable to a power socket. If the flexible power cable and plug of this
appliance is damaged, it must be replaced by the special APARICI power cable reference 91027.
It is also essential to always install an omnipolar switch to the power supply network, with a minimum
opening between the contacts of 3 mm.
To carry out the installation with direct current (DC), these models must be connected to a field of
photovoltaic solar panels mounted in series. The panel field has to be two units (83.4V - 800W - 9.6 A) based on
standard 400W - 41.7 V - 9.6 A panels in PTC conditions (not included).
The installation must have the necessary protections not included in the product. Specifically, 12A fuses
both in the positive and negative wires and ensure that all components of the direct current installation are class II.
As an alternative, a switch against indirect contacts (insulation monitor) can be installed. None of these additional
components are included.
The single-line diagram of the SH model is shown below together with the assembly of the collector field: