6. Set the desired value and confirm by pressing the "OK" key:
Address
Range: 1~153
-
OK
4.4 PHASE 2 - SERIAL ADDRESS SETTING OF THE HMG UNITS
To connect the units to the supervisor, it is necessary to set the correct modbus address to be assigned to the unit; please note that on VMF-E6, VMF-E5 or MULTICONTROL
supervisors, the addresses dedicated to the chillers are: 200, 201, 202, 203. For more information, refer to the documentation of the supervisor to be used.
To set a supervision address on the units, the following steps must be followed:
1. Press the "FUNCTION" button on the user interface of the HMG heat pump:
Mode: Cool
On-line units:0
FUNCTION
2. Press "Next" (the arrow button on the right of the page) until you reach the "Address" parameter:
FUNCTION(3/3)
Remote monitoring address: 16
Resetting: Enter
Field commissioning: Enter
Factory commissioning: Enter
3. Select the "Address" parameter:
Remote monitoring address
RANGE: 1~255
1
2
3
6
7
8
Set the desired value and confirm by pressing the "OK" key.