FireClass
Technical specification
Type Identification
Value:
System Compatibility:
Environment:
Operating Temperature:
Storage Temperature:
Operating Humidity:
Dimensions (HxWxD):
Mounting Require-
ments:
Battery Requirements:
Standby Current:
Alarm Current:
Recommended Wire
Size:
Maximum wiring resistance
Monitored circuit
Addressable Device Conditions:
- Normal
- Active
- Short Circuit wiring fault
- Open Circuit wiring fault
- Device Type Invalid
- Device No Response
Electromagnetic Compatibility
The FC410CIM complies with the following:
product family standard EN50130-4 in respect
of Conducted Disturbances, Radiated Immu-
nity, Electrostatic Discharge, Fast Transients
and Slow High Energy;
EN61000-6-3 for emissions.
Fixing Instructions Doc. version 4.0
ENGLISH
146
Use with FC Fire
Alarm Controllers
Indoor
Application only
-25 °C to +70 °C
-40 °C to +80 °C
Up to 95% non-
condensing
87 x 148 x 14 mm
One FC backbox
surface mount
0.505mA
4.5mA
2
Min. 1.5mm
2
Max. 2.5mm
10 Ohm
Introduction
The FC410CIM FC Addressable Contact Input
Module is designed to monitor fire contacts such
as extinguishing system control, ventilation con-
trol, fire door control etc. The FC410CIM can be
configured as:
Two spur circuits (Class B) monitoring multi-
ple normally open contacts, with short circuit
giving a fault output.
Two spur circuits (Class B) monitoring single
normally closed contacts, with short circuit
giving a fault output.
Two spur circuits (Class B) monitoring multi-
ple normally open contacts, with short circuit
giving an alarm.
Features
FC410CIM monitoring features include the
following configurable items:
Identifies all monitored contacts and signals
to the Fire Controller the status of monitored
contacts and wiring to the contacts.
Can monitor a single normally closed contact.
Can monitor two Class B spur circuits.
A monitored contact going to the active state,
on either spur circuit, will cause FC410CIM to
report the Active State back to the FireClass
controller.
An LED reports FC410CIM status to the user.
The LED lights when the contact monitored
by the FC410CIM has switched to the active
(off normal) state.
The LED when normally off, will pulse when
the FC410CIM is polled by the controller.
Wiring & installation notes
The following notes apply:
1 There are no user-required settings (such as
switches or headers) on FC410CIM.
2 All wiring must conform to the applicable
standards.
3 All conductors to be free of earths.
4 Fit the PCB to the FC470CV cover.
5 Connect wiring to the monitored contact. For
FC410CIM typical wiring configurations see
Figures 3 to 5.
FC410CIM