FC410CIM
6 Verify the correct polarity of wiring before
connecting the FC410CIM to the addressable
loop circuit.
Note: Refer to Fig. 3.
1 If only one circuit is used, the other circuit
must be terminated with 200/100 ohm resis-
tors in parallel or a single 68 ohm EOL resis-
tor.
2 FireClass Console configuration selection -
Style C (normally closed).
Note: Refer to Fig. 4.
1 If only one circuit is used, the other circuit
must be terminated with 200 ohm EOL resis-
tor.
2 FireClass Console configuration selection -
Style C (normally open).
Note: Refer to Fig. 5.
FireClass Console configuration selection - Style
B (normally open). If only one circuit is used, the
other circuit must be terminated with 200 ohm
EOL resistor.
Installation to FC470CV double gang
cover
1 Assemble the FC410CIM to M520 Double
Gang cover, using the four screws and was-
hers provided.
2 Fit cover onto FC backbox.
Address settings
The FC410CIM has a default factory set address
of 255, this must be set to the loop address of
the device using the FC490ST Loop Service
Tool. The FC410CIM may be programmed with
the address prior to being installed by using the
internal programming port (see Fig.1) or after
being installed by using the programming port on
the front cover (see Fig.2).
Note: When the address has been programmed,
take note of the device location and address
number, to include on site drawings.
Note: This device use one address only on the
loop.
4/12
Cabling
Cables are to be selected in accordance with the
system design document and the requirements
of the applicable standard. Two pairs of connec-
tion terminals (L+ and L-) are provided on the ter-
minal block. These terminals are used for con-
necting the module on to the addressable circuit.
The maximum section of the cable that can be
connected at any one terminal is 2.5mm
section is calculated based on the characteristics
of the cable and the load.
Associated equipment
The module fits onto a standard dual-gang back-
box.
Ordering information
FC410CIM:
Contact Input Module
FC470CV:
Double-Gang Cover
Recycling information
Customers are recommended to dispose of their
used equipments (panels, detectors, sirens, and
other devices) in an environmentally sound man-
ner. Potential methods include reuse of parts or
whole products and recycling of products, com-
ponents, and/or materials.
Waste electrical and electronic
equipment (WEEE) directive
In the European Union, this label indi-
cates that this product should NOT
be disposed of with household
waste. It should be deposited at an
appropriate facility to enable reco-
very and recycling.
The manufacturer reserves the right to change
the technical specifications of this product
without prior notice.
Fixing Instructions Doc. version 4.0
FireClass
2
. The