English
I Front view with operating controls
Adjustment of the time range by selecting the max. value:
Range
Max. value
0.15 - 3 s
>> 3 s
1.5 - 30 s
>> 30 s
15 - 300 s
>> 300 s
0.15 - 3 min
>> 3 min
1.5 - 30 min
>> 30 min
15 - 300 min
>> 300 min
1.5 - 30 h
>> 30 h
15 - 300 h
>> 300 h
0.05 - 1 s
>> 1 s
0.5 - 10 s
>> 10 s
5 - 100 s
>> 100 s
0.5 - 10 min
>> 10 min
0.05 - 1 h
>> 1 h
0.5 - 10 h
>> 10 h
5 - 100 h
>> 100 h
Selection of the function on 700-FSM6-EX, 700-FSM7-EX,
700-FSM8-EX
Functions: see III
Indication of operational states with LEDs
U/T: green LED
- Status indication of control supply
voltage and timing
V
W
R: yellow LED
- Status indication of output relay
V
R1/R2: yellow LED - Status indication of output relays
1 and 2
V
II Electrical connection
For the rated control supply voltage and the circuit
diagram, see label at the side of the unit.
A1-A2
Control supply voltage U
A1-B1
Control input (voltage-related triggering)
15-16/18
1st c/o contact
25-26/28
2nd c/o contact
yellow
dial
white
dial
Control supply voltage applied
Time delay is running
energized
energized
s
III
Functions
700-FSK6-EX
K
One shot with B1
t
adjusted time delay
700-FSM6-EX, 700-FSM7-EX
A
ON-delay
t
adjusted time delay
A+
Accumulative ON-delay
t
adjusted time delay
B
OFF-delay with auxiliary voltage
t
adjusted time delay
C
ON-delay and OFF-delay, symmetrical
t1 adjusted ON-delay
t2 adjusted OFF-delay
D
Impulse-ON
t
adjusted pulse time
E
Impulse-OFF with auxiliary voltage
t
adjusted pulse time
FG Flasher, starting with ON or OFF
t
adjusted flashing time
L
Pulse former
t
adjusted pulse time
T
ON/OFF-function
OFF-Function: Time sector = 300 h
700-FSM6-EX:
OFF-Function: Time sector = 100 h
Y1
Star-delta change-over with impulse function
(not on 700-FSM6-EX)
t1 adjusted starting time
t2 fixed transition time of 50 ms
700-FSM8-EX
A
ON-delay
t
adjusted time delay
D
Impulse-ON
t
adjusted pulse time
F
Flasher, starting with ON
t
adjusted flashing time
G
Flasher, starting with OFF
t
adjusted flashing time
I
Fixed impulse with adjustable time delay
t1 adjusted time delay
t2 fixed pulse time of 500 ms
M
Adjustable impulse with fixed time delay
t1 adjusted pulse time
t2 fixed time delay of 500 ms
T
ON/OFF-function
OFF-Function - time sector = 300 h
Legend
t3
Pause timing
LED
Green LED flashes whilst timing
Control supply voltage not applied /
G
output contact open
Control supply voltage applied /
B
output contact closed
6