Additional information and notes on safety
Products:
Electronic timers 700-FSK6-EX, 700-FSM6-EX, 700-FSM7-EX,
700-FSM8-EX
The devices are suitable for installation in a zone 2 potentially
explosive area.
Directives:
Equipment or Protective System intended for use in Potentially
Explosive Atmospheres Directive 2014/34/EU
Product or Protective System Intended for use in Potentially Explosive
Atmospheres UKSI 2016:1107 (as amended by UKSI 2019:696) –
Schedule 3A, Part 1
Marking / Classification:
I
II 3G Ex ec nC IIC T4 Gc
Type Examination Certificate
ULD 22 ATEX 2837X
UL 22 UKEX2625X
IECEx ULD 22.0023X
2A 32VDC MAX.
Class I Division 2 Groups A, B, C, D
Class I Zn2, Group IIC
Temp.Code T4
Input A1/A2: 24...240Vac/dc (ac: -15%/+10%, dc: -25%/+10%)
Operating and installation instruction:
General information and installation guidelines must be taken from
the operating and installation instructions delivered with the product
and from the main catalogue.
WARNING - EXPLOSION HAZARDS!
Warning - Do not connect or disconnect equipment unless power has
been removed or the area is known to be non-hazardous.
The device must be installed in a suitable tool-secured enclosure.
Installation in a housing with minimum protection IP54 according to
EN IEC 60079-0.
The enclosure must ensure sufficient light / UV protection for the
internal components.
The timers are maintenance free. Opening of the timers and replace-
ment of components is prohibited!
In case of damage or malfunction, the device must be stopped and
removed from the hazardous area.
Components attached or installed (terminals, bushings, cable entry
fittings, connectors) must be of a technical standard that complies
with the specifications requested in the particular application, and
a separate examination certificate must have been issued for them.
The operating conditions specified in the component certificates
must be followed.
Installation onto a DIN-rail according to EN 60715 with the input
terminals A1 on the top and A2 on the bottom of the device.
The maximum ambient temperature must be observed in the final
a
Ind.Cont.Eq
A
For Hazardous
Locations
E10314
Français
I Face avant et dispositifs de commande
Réglage de la plage de temporisation par sélection de la valeur
maximale:
Plage
Valeur maximale
0,15 - 3 s
>> 3 s
1,5 - 30 s
>> 30 s
15 - 300 s
>> 300 s
0,15 - 3 min
>> 3 min
1,5 - 30 min
>> 30 min
15 - 300 min
>> 300 min
1,5 - 30 h
>> 30 h
15 - 300 h
>> 300 h
0,05 - 1 s
>> 1 s
0,5 - 10 s
>> 10 s
5 - 100 s
>> 100 s
0,5 - 10 min
>> 10 min
0,05 - 1 h
>> 1 h
0,5 - 10 h
>> 10 h
5 - 100 h
>> 100 h
Sélection de la fonction pour 700-FSM6-EX, 700-FSM7-EX,
700-FSM8-EX
pour les fonctions, voir III
Indication de fonctionnement par LED
U/T: LED verte
- Indication de la tension d'alimentation de
commande et temporisation
V
W
R: LED jaune
- Indication de l'état du relais de sortie
V
R1/R2: LED jaune - Indication de l'état des relais de sortie
1 et 2
V
II Raccordement électrique
Pour la tension assignée d'alimentation de
commande et pour le schéma des connexions
voir l'étiquette placée sur le côté du relais
A1-A2
Tension d'alimentation de commande U
A1-B1
Entrée de commande (activation par tension)
15-16/18
1er inverseur
25-26/28
2ème inverseur
échelle
jaune
échelle
blanche
Tension d'alimentation de com-
mande appliquée
Temporisation en cours
activé
activé
s
7