Water tank full:
If the water tank is full, its indicator will light on and the buzzer
sounds around 15 rings. Press any key and the beep
At this time, the unit has stop running.
Press any key and the alarm will stop immediately.
Take out and pour water tank. Fig.2
Put the water tank back in the unit and the dehumidifier will start
working automatically and the original machine´s operating status
is restored.
Caution: Do not remove the floater in the water tank, otherwise, the
water sensor will not be able to sense the water level so that it
cannot operate normally. Fig.2
Anti-defrost function
This function will be activated when the ambient temperature falls
below 16°C.
The display will show „ DEF ".
If the room temperature <5°C, the controller stops.
It will be activated for a period of 10 minutes every 30 minutes
between 5-12°C.
It will also be activated for a period of 10 minutes every 45 minutes
between 12-16°C.
When the room temperature is higher than 16ºC, the temperature of
the coil is detected and the operation is performed according to the
temperature of the coil, as follows:
The compressor is running for 30 minutes, the coil temperature is
detected.
If the coil temperature is ≤ 1°C, the defrosting is stopped for 10
minutes.
Compressor delay protection:
Every time the boot compressor is allowed to start immediately;
After the compressor is shut down, start it again, with at least a
3 minute interval.
CONTINUOUS DRAINAGE
Connect a plastic hose (with an inner diameter of 10 mm) to the
continuous drainage port via the small hole.
Water can be drained continuously.
Please check if the pipe is stably connected with the drainage