Before Installation
Safety Requirements
Be sure to preview the standard operating procedures (SOP) and ensure local building and elec-
trical codes are reviewed before installing the DC Wallbox charger.
The DC Wallbox charger should be installed by a qualified technician according to the instruction
manual and local safety regulations.
Use appropriate protection when connecting to the main power distribution cable.
Disconnect switch for each ungrounded conductor of ac input shall be provided by others in
accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION!
!
T
O REDUCE RISK OF FIRE FOR
N
E
ATIONAL
LECTRIC
INSTALLED WITH A RATED CURRENT OF
CAUTION!
!
T
O REDUCE RISK OF FIRE FOR
E
C
LECTRIC
ODE
A RATED CURRENT OF
CAUTION!
!
T
O REDUCE RISK OF FIRE FOR
E
C
LECTRIC
ODE
A RATED CURRENT OF
Note:
Depends on local regulations requirements.
Installation and Operation Manual
1
200V
PHASE
C
, ANSI/NFPA 70,
ODE
175A.
3
480V
PHASE
, ANSI/NFPA 70,
THE UPSTREAM CIRCUIT BREAKER SHOULD BE INSTALLED WITH
40A.
3
208V
PHASE
, ANSI/NFPA 70,
THE UPSTREAM CIRCUIT BREAKER SHOULD BE INSTALLED WITH
100A.
-277V
,
AC
AC INPUT
IN ACCORDANCE WITH THE
THE UPSTREAM CIRCUIT BREAKER SHOULD BE
,
AC INPUT
IN ACCORDANCE WITH THE
,
AC INPUT
IN ACCORDANCE WITH THE
7
Before Installation
N
ATIONAL
N
ATIONAL