Single-phase
Wiring the 240 / 277V Models
Conduit hub and conduit size M50 according to EN 61386-24.
Connect the power wires of 2 x RNB70-10 ring terminal with cable lugs to the input termi-
nal marked with "L" and "N" using 2 x M10.0 screws with 88.4 lb-in Torque force.
Connect the ground wire of RNB14-6 into the earth terminal marked with ground symbol
(
) using 1 x M6.0 screw with 17.7 lb-in Torque force.
Three-phase
Wiring the 480V Model
Conduit hub and conduit size M50 according to EN 61386-24.
Connect the power wires of 4 x RNB14-6 ring terminal with cable lugs to the input terminal
marked with "L1", "L2", "L3" and "N" using 4 x M6.0 screws with 28.7 lb-in Torque force.
Connect the ground wire of RNB14-6 into the earth terminal marked with ground symbol
(
) using 1 x M6.0 screw with 17.7 lb-in Torque force.
Wiring the 208V Model
Conduit hub and conduit size M50 according to EN 61386-24.
Installation and Operation Manual
L N
PE
L1 L2 L3 N
PE
L1 L2 L3
PE
15
Making the Connection