Descargar Imprimir esta página

TEXA TX-i40 Manual De Instrucciones página 22

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ENG
3.2 Display
The following drawing shows the layout of the icons on the TX-i40 display:
The following table illustrates the meaning of the icons on the display:
Icon
Meaning
Compressor
Condensing
fan
Heating
element
(Optional)
Alarm
Energy Saving
Gear
Degrees
Celsius
Degrees
Fahrenheit
Unit of
measurement
%
On/stand-by
Description
ON if the compressor is running
OFF if the compressor is not running
BLINK if timers are in progress
FAST BLINK if the compressor is running in support of a high load (connection in sequence configuration)
ON if the fan is running
BLINK if the Pre- or Post-ventilation cycle is in progress
OFF if the fan is not running
ON if the heating element is on
OFF if the heating element is off
BLINK if timers are in progress
ON if at least one manual reset alarm is active
BLINK if only automatic reset alarms are active
OFF if no alarm is active
ON if the evaporator fan economy cycle is in progress
OFF if the evaporator fan economy cycle is not in progress
ON if the device is not in primary display
BLINK maintenance indication
OFF during normal operation
Unit of measurement °C
Unit of measurement °F
OFF
ON if the regulation is not active
OFF if the regulation is active
22

Publicidad

loading

Productos relacionados para TEXA TX-i40