Ecoflam MAX GAS 170 P Manual De Uso página 12

Ocultar thumbs Ver también para MAX GAS 170 P:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 36
EN
A
B
A
!
Risk of air blast!
Continuously check CO, CO 2 and soot emissions when adjusting the output of the burner. Optimise combustion values in the
event of CO formation. CO must not exceed 50 ppm.
Gas pressure diagrams in appendix
Minimum gas pressure required are
indicated in the diagrams in the appendix.
These values have been determined in
our test labs and are useful for the first
switch-on as final setting must be done
using a combustion analyzer.
How to read and adjust the values:
- determine the output required
- determine the combustion chamber back-
pressure
- read the minimum gas pressure required
in the diagrams in appendix.
Optimising combustion values
The factory setting shall be modified
12
www.ecoflam-burners.com
B
according to the output requeired.
The diagrams of air/head setting
that are available in the appendix
of this manual are a guide for ensuring
that the burner functions as well as
possible.
output (kW)
Air damper setting (A).
To act on the screw A in figure:
• to increase output, turn screwdriver
counterclockwise.
• to reduce output, turn screwdriver
clockwise.
Note: screw B not used.Firing head
setting (B).
To act on the screw in fi gure:
• turn Allen key till you reach the
requested value (index 0-4,5).
Adjustment of gas solenoid valve
Refer to the gas train manual for the gas
setting of the gas train selected.
N.B. observe the minimum required
flue gas temperature specified by the
boiler manufacturer and the requirements
demanded of ue gas ducts for avoiding
condensation.
P1 = Minimum gas pressure with gas governor
completely open.
P2 = Minimum gas pressure.
420010372900

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Max gas 250 p

Tabla de contenido