Body
Fixing hole
Screws M5x20
(Accessory for the panel)
Colorless
trans parent pipe
Caution
•
Use adjustable mounting hooks to make sure that the unit body is level,
otherwise it may cause water to leak. Calibrate the levelness of the unit
using a spirit level or polyethylene tube filled with water. See Figure 3.9.
•
The unit is equipped with a built-in water discharge pump and float
switch. Do not tilt the unit in the direction of the drain pan; otherwise,
the float switch may malfunction and cause water leakages.
Dimensions of unit
647(Panel)
Unit: mm
570(Body)
545(Hook-location)
Hook hole
Central hole
Installation paper board
Figure 3.8
Horizontal
indicator
Figure 3.9
Drainage side
A
280
Drainage Pipe
Φ25(OD)
Figure 3.10
Hook
Body
Nut
Ceiling
Panel
Body
Ceiling
Caution
•
All the figures in this manual are for illustration purposes only. The
actual air conditioner you purchased may not have the same
appearance and functions as those listed in these figures. Please refer
to the actual product model.
3.3 Panel Installation
3.3.1 Remove the air inlet grille
(1)
Press the two grille locks inwards in the direction indicated
by the arrows at the same time to lift it up (Figure 3.12).
Grid switch
(2)
Raise the air inlet grille to about 45°, and remove the grille.
Caution
•
Do not place the panel such that it faces downwards or leans against
the wall. Do not place it on a protruding object either.
•
Do not hit or squeeze the air deflector.
6
Drainage pipe
Φ25(OD)
Gas pipe
Φ12.7(OD)
Liquid pipe
Φ6.35(OD)
600
L=30~40
Figure 3.11
Figure 3.12
Figure 3.13
V.2