DRAIN INSTALLATION
7
The Santa Fe Ultra120V generates condensate.
Place a secondary drain pan with a float switch under the dehumidifier if it is suspended above a finished area or
above an area where water leakage could cause damage.
The Santa Fe Ultra120V contains an internal drain trap for proper dehumidifier operation. Install a 3/4" threaded
male NPT adapter to the external condensate fitting. Install a drain pipe assembly utilizing 3/4" PVC pipe to
transport the condensate to a drain. Pitch of drain should be 1" per 10'. An optional condensate pump kit is
available for use with the Santa Fe Ultra120V and may be installed if lift is required to dispose of condensate.
Condensate is automatically pumped to a remote location when the water level in the pump's reservoir rises to
close the float switch.
The pump also contains a safety float switch. If the pump fails, this switch opens the common control circuit
and stops water production before the reservoir overflows.
10
Santa Fe ULTRA120V Installation & Operation Instructions
Supply
Air
Outlet
Side View
3/4" FPT
Fitting