DUCTING TO HVAC SYSTEMS (Closet Installations)
9
CAUTION!
PLEASE NOTE: RETURN TO RETURN INSTALLS ARE TO BE CONSIDERED LAST RESORT OPTIONS AND ARE
NOT RECOMMENDED. THE DEHUMIDIFIER WILL HEAT THE AC COOLING COILS WHICH DIMINISHES THE
AMOUNT OF WATER THE AC SYSTEM WILL REMOVE WHEN OPERATING. PLEASE CHECK YOUR LOCAL
CODES PRIOR TO INSTALLING.
2. Alternative Closet Installation
If the Recommended Closet Installation is not possible, there are alternative installation options available.
No inlet duct is required. Air is pulled through the louvers or grille from the living space.
Install a 6" insulated duct from outside, teeing into the 8" return duct of the Santa Fe Ultra Series
Dehumidifier to provide outdoor air ventilation (optional).
Control should be placed in a central location or the on board control can be used for this installation.
a. Central Return to HVAC Return
Duct the supply of the Ultra Series
Dehumidifier to the return side of the
existing HVAC system.
In a central return system, the HVAC
fan must run when the dehumidifier is
running.
800.533.7533 | Santa-Fe-Products.com
Ultra Series
HVAC
Return
Ultra Series
Supply
Santa Fe ULTRA120V Installation & Operation Instructions
HVAC
Supply
Return
Motorized
Damper
Optional Outdoor
Air Intake
Duct Cover
Plate