Descargar Imprimir esta página

Honeywell Home FocusPRO M37842 Manual De Instrucciones página 4

Publicidad

Idiomas disponibles

Idiomas disponibles

FocusPRO
Thermostat Installation Guide
®
Installer setup tables
Setup function
0
Zone number
1
System type
2
Changeover valve
(O/B terminal)
3
Fan control
(conventional heat)
4
Backup heat
(EIM only)
5
Stage 1 heat cycle
rate (CPH: cycles per
hour)
6
Stage 2 heat cycle
rate (CPH)
7
Stage 3 heat cycle
rate (CPH)
8
Emergency heat cycle
rate (CPH)
9
Stage 1 compressor
cycle rate
10 Stage 2 compressor
cycle rate
11 Heat pump type
(EIM only)
12 Manual/Auto
changeover
13 Adaptive Intelligent
Recovery™
14 Temperature
display
15 Compressor off time
16 Schedule format
69-2092EFS—11
Settings & options (factory default in bold)
0
No zoning (single thermostat used with THM5421R or THM5320R
EIM) [Options: select zone 1, 2, 3 or 4]
0
1 heat/1 cool conventional
1
1 heat/1 cool heat pump (no aux. heat)
2
Heat only (includes Series 20)
3
Heat only with fan
4
Cool only
5
2 heat/1 cool heat pump
6
2 heat/2 cool conventional
7
2 heat/1 cool conventional
8
1 heat/2 cool conventional
9
2 heat/2 cool heat pump
10
3 heat/2 cool heat pump
0
O/B terminal controls valve in cooling
1
O/B terminal controls valve in heating
0
Gas/Oil heat (equipment controls fan)
1
Electric furnace (thermostat controls fan)
1
Electric backup heat
0
Fossil fuel backup heat
5
Gas or oil furnaces (less than 90% efficiency)
1
Steam or gravity systems
3
Hot water systems & furnaces of over 90% efficiency
9
Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5
Gas or oil furnaces (less than 90% efficiency)
1
Steam or gravity systems
3
Hot water systems & furnaces of over 90% efficiency
9
Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5
Gas or oil furnaces (less than 90% efficiency)
1
Steam or gravity systems
3
Hot water systems & furnaces of over 90% efficiency
9
Electric furnaces
[Cycle rate options: 1 to 12 CPH]
9
Electric furnace
[Cycle rate options: 1 to 12 CPH]
3
Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
3
Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
0
Air to Air Heat Pump
1
Geothermal heat pump
0
Manual (User options: Heat/Cool/Off)
1
Automatic (User options: Heat/Cool/Auto/Off)
Applies only to Model TH6320
0
Off
1
On
0
Fahrenheit
1
Celsius
5
5 minutes (Heat On/Cool On flashes during off time)
[Options: 0 to 4 minutes]
Applies only to Model TH6320
0
Weekday/weekend program schedule
1
Weekday/Saturday/Sunday program schedule
4

Publicidad

loading