Factory setting = OFF
Factory setting 5 = OFF
Factory setting 6 = ON
Factory setting = OFF
Factory setting = ON
ASB mode
ON
: ASB mode on
OFF : ASB mode off
Battery type / Charge program (12V / 24V / 48V)
5 = OFF : Battery type = Flooded
6 = OFF
Absorption voltage = 14.4V / 28.8V / 57.6V
Float voltage = 13.5V / 27.0V / 54.0V
5 = ON : Battery type = GEL
6 = OFF
Absorption voltage = 14.2V / 28.4V / 56.8V
Float voltage = 13.5V / 27.0V / 54.0V
5 = OFF : Battery type = AGM
6 = ON
Absorption voltage = 14.3V / 28.6V / 57.2V
Float voltage = 13.3V / 26.6V / 53.2V
5 = ON : Battery type = Custom (created by Dashboard)
6 = ON
Absorption voltage = set by Dashboard
Float voltage = set by Dashboard
AC Input Power Boost
ON
: AC Input Power Boost on
OFF : AC Input Power Boost off
Models : PSC1600-1800
Bypass remote switch (Bypasses the remote switch
connection when no remote switch is connected)
ON
: Remote switch connection terminals are bypassed
OFF : remote switch connection terminals are open. A
remote switch must be connected and switched ON
in order to activate the Powersine Combi. The local
on/off switch on the frontpanel always overrides the
remote switch. So in order to use the remote switch,
the local on/off switch must be in the 'on' or
'charger only' position.
Models : PSC2000-3500
Ground switch/relay
ON
: Ground switch is enabled
OFF : Ground switch is disabled