6. TROUBLESHOOTING GUIDELINE
Please see the table below if you experience any problems with the Powersine Combi and/or
the installation.
Problem
Powersine Combi is not
working at all.
The charger mode is not
working (AC transfer switch
does not activate either).
The battery is not being
charged up to it's maximum
capacity.
Possible cause
Main switch in Off (0)
position.
Remote switch or Universal
Remote Control have
deactivated the Powersine
Combi.
Poor contact between the
Powersine Combi battery
wires and the battery
terminals.
Blown DC fuse.
Very poor battery condition.
The AC input voltage or
frequency are out of range or
too unstable.
Charger mode and/or the AC
transfer switch are disabled
during setup using
Dashboard.
Incorrect absorption charge
voltage setting.
Incorrect charge current
setting.
Too much voltage loss in
battery cables and/or
connections.
20
Remedy
Push the power switch in the
'I' or 'II' position.
Activate the Powersine
Combi remotely or check DIP
switch 8 or 10 for correct
setting.
Clean battery terminals or
Powersine Combi wire
contacts. Tighten battery
terminal screws.
Check battery fuse or
internal Powersine Combi
fuse (PSC1600-1800 only).
Replace battery.
Make sure that the AC input
voltage is between 185V -
270V and the frequency
between 45Hz – 65Hz
(assuming standard settings)
Enable Charger mode and
the AC transfer switch using
Dashboard.
Check DIP switch 5 and 6 for
correct settings. Or adjust
the absorption voltage using
TBS Dashboard.
Adjust the charge current
using the Universal Remote
Control or TBS Dashboard.
Typically, the charge current
should be set to 10%-20% of
the total battery capacity
Make sure that the battery
cables have a large enough
diameter. Check if all DC
connections are solidly
made.

Publicidad

loading