Descargar Imprimir esta página

EAS ELECTRIC CND Serie Manual De Instrucciones página 29

Publicidad

Idiomas disponibles

Idiomas disponibles

Expansion hook
4
anchor
Mounting hook
5
Tie
6
1. Before Installation
1. Determine the route to move the unit to the installation site.
2. First unseal and unpack the unit. Then hold the four seats of the
hanger to move the unit. Refrain from exerting force on other parts
of the unit, especially the refrigerant piping, water discharge
piping, and plastic parts.
3. The Fresh Air Processing Unit can be used either independently
or in conjunction with other types of indoor unit. If used
independently, the total capacity of the Fresh Air Processing Units
must be between 50% and 100% of that of the outdoor units. If
used in conjunction with other types of indoor unit, the total
capacity of the indoor units and Fresh Air Processing Units must
be between 50% and 100% of that of the outdoor units and the
total capacity of the Fresh Air Processing Units must not exceed
30% of that of the outdoor units.
2. Choosing an Installation Site
2.1 Choose a site that fully complies with the following conditions
and user requirements to install the air conditioning unit.
 Well ventilated.
 Unobstructed airflow.
 Strong enough to bear the weight of the indoor unit.
 Ceiling has no obvious slant.
 There is sufficient space for repair and maintenance work to be
carried out.
 No leakage of flammable gas.
 The length of the piping between the indoor and outdoor units is
within the permitted range (refer to the manual on installation of
the outdoor unit).
 The static pressure of the air duct of the indoor unit is within the
permitted range (see 6.2 Fan Performance).
Caution
If the indoor ambient temperature and relative humidity
exceed 30°C and 80%, attach insulation materials at a
thickness greater than 10 mm to the unit body.
2.2 Install with M10 or W3/8 lifting bolts.
2.3 The space required for installation (unit: mm) is shown in
Figure 2.1 and Figure 2.2:
Side face (wall)
Maintenance room
Air outlet side
Electric control
box assembly
Maintenance
room
Side face (wall)
Figure 2.1
M10
M10
To purchase based on actual
project requirements.
Air return side
Inspection: 600 mm X 600 mm
To purchase based on actual
project requirements.
To purchase based on actual
project requirements.
To purchase based on actual
project requirements.
Air outlet side
Electric control
box assembly
Ceiling
Ensure that the minimum slope for water
discharge is more than 1/100, and that the unit
body slopes down towards the drainage side.
3. Indoor Unit Installation
Make sure that only specified components are used for the installation
works.
3.1 Installation with Lifting Bolts
Use different bolts for the installation depending on the installation
environment.
Wooden structure
Square bar
material
Original concrete slab structure
Use embedded bolts, and pull bolts.
3
For installation of
indoor unit.
For installation of
indoor unit.
Tie for connecting wire
Air return side
For Inspection
Figure 2.2
Beam
Ceiling
Lifting bolt
Figure 3.1
Figure 3.2

Publicidad

loading