SW4
In heating mode when the set temperature has been
SW4
reached, the fan operates in a 4 minutes off / 1 minute on
[
]
00
repeating cycle
In heating mode when the set temperature has been
SW4
reached, the fan operates in an 8 minutes off / 1 minute
[
]
01
on repeating cycle
In heating mode when the set temperature has been
SW4
reached, the fan operates in a 12 minutes off / 1 minute
[
]
10
on repeating cycle
In heating mode when the set temperature has been
SW4
reached, the fan keep running at low fan speed
[
]
11
SW5
In heating mode fan does not run when indoor heat
SW5
exchanger mid-point temperature is 15°C or below
[
]
00
In heating mode fan does not run when indoor heat
SW5
[
]
exchanger mid-point temperature is 20°C or below
01
In heating mode fan does not run when indoor heat
SW5
exchanger mid-point temperature is 24°C or below
[
]
10
In heating mode fan does not run when indoor heat
SW5
exchanger mid-point temperature is 26°C or below
[
]
11
SW6
SW6
Heating mode temperature compensation is 6°C
[
]
00
SW6
Heating mode temperature compensation is 2°C
[
]
01
SW6
Heating mode temperature compensation is 4°C
[
]
10
Heating mode temperature compensation is 0°C (use
SW6
follow me function)
[
]
11
SW7_1
SW7
Reserved
[
]
0
SW7_2
SW7
Unit with capacity less than 28kW
[
]
0
SW7
Unit with capacity equal or more than 28kW
[
]
1
J1
Auto restart function enabled
Auto restart function disabled
0/1 definition of each dial code switch:
means 0
Note
All DIP switches (including the capacity DIP switch) have been
configured before delivery. Only a professional maintenance
personnel should change these settings.
Improper DIP switch settings may cause condensation, noise, or
unexpected system malfunction.
The default DIP switch setting is based on the actual unit.
8.4 Error Codes and Definitions
Error
code
E0
E1
E2
E3
E4
E6
E7
Eb
Ed
EE
FE
9. Test Run
9.1 Things to Note Before Test Run
1) Indoor and outdoor units are properly installed;
2) Piping and wiring are correct;
3) No leakage from the refrigerant piping system;
4) Water discharge is smooth;
5) Insulation is complete;
6) Grounding line has been properly connected;
7) Piping length, and amount of refrigerant filled have been recorded;
8) The voltage of the power supply is the same as the rated voltage
of the air conditioner;
9) No obstacles at the air inlet and outlet of the indoor and outdoor
units;
10) Cut-off valves for the gas and liquid ends are opened;
11) Connect to the power supply to let the air conditioner warm up first.
9.2 Test Run
Use wired/remote controller to control and operate the air conditioner
in the cooling mode. Check the following items according to the
manual. If there is any fault, troubleshoot by referring to the section
"Air Conditioner Errors and Causes" in the manual.
9.2.1 Indoor unit
1) Wired/remote controller switch is operating normally;
2) Function keys of the wired/remote controller are operating normally;
3) Room temperature regulation is normal;
4) LED indicator is on;
5) Key for manual operation is normal;
6) Water discharge is normal;
7) No vibration and strange sounds during operation;
9.2.2 Outdoor unit
1) No vibration and strange sounds during operation;
2) If the wind, noise and condensation affect the neighbours;
3) Any refrigerant leakage.
means 1
Once the power is connected, when the unit is turned on or
started immediately after the unit is turned off, the air conditioner
has a protective function which delays the start of the
compressor by 3 minutes.
17
Content
Mode conflict
Communication error between indoor and outdoor units
Indoor ambient temperature sensor (T1) error
Indoor heat exchanger mid-point temperature sensor
(T2) error
Indoor heat exchanger outlet temperature sensor
(T2B) error
Fan error
EEPROM error
Indoor EEV coil error
Outdoor unit error
Water level error
Indoor unit has not been assigned an address
Note