Vent module for 3 groups LM3G
Terminal assignment
Top terminal row
(as a rule the terminal board for the fitter)
Bottom terminal row
(as a rule the terminal board for the fitter
Connections
Vent switch (A)
Vent switch (B)
Vent switch (C)
12
Vent switch LTA25/..
LTA25/..
LTA25/..
Numbering the connection terminals follows the same
principle for all MZ2-modules (exception: Power supply
unit NM16A).
Module-view:
Starting at , top left.
The numbering is continued at each deeper level, starting
at the left.
Numbering of the bottom terminal rows is continued as
per the procedure described above at
Warning: The module must never be fitted on
the top hat rail when the supply is switched on; this will
lead to damage to the module.
Clamp 1: Vent switch A, switch CLOSE
Clamp 2: Vent switch A, switch OPEN
Clamp 3: Vent switch A, power supply
Clamp 4: Vent switch A, signal OPEN
Clamp 5: Vent switch B, switch CLOSE
Clamp 6: Vent switch B, switch OPEN
Clamp 7: Vent switch B, power supply
Clamp 8: Vent switch B, signal OPEN
Clamp 9: Vent switch C, switch CLOSE
Clamp 10: Vent switch C, switch OPEN
Clamp 11: Vent switch C, power supply
Clamp 12: Vent switch C, signal OPEN
.
05/24999653