Error detecting codes
Supply + 3.3 V: 10 times flash
The continuous self test has discovered an internal error.
Remedial Measures:
- Send the module into the service department.
Warning: Further safe operation can no longer be guaranteed!
Supply + 24 V: 11 times flash
The continuous self test has discovered a faulty supply voltage.
Remedial Measures:
- Check fuses on the power pack module.
- Check that the module is snapped onto the rail correctly.
- Check that the bus connector on the top hat rail is ok.
- Check if the wiring top hat rail to power pack module is ok.
- If nothing helps replace the module.
Ventilation configuration: 16 times flash
The ventilation function selected with the aid of the MZ2 configuration software contradicts the
DIP-Switch setting or the DIP-Switch setting is invalid.
Remedial Measures:
- Check DIP-Switch setting and configuration settings and alter.
- See also: MZ2 configuration program and DIP-Switch bar.
Technical data
Operating voltage module:
Power consumption module:
Power consumption:
Power consumption:
Power consumption:
Temperature range:
Humidity range:
Protection class:
Vent switch
Switching current OPEN:
Switching current CLOSED:
Signal outputs
Ventilation status:
05/24999653
15 - 32 V DC
5.0 mA (at 27.5 V operating voltage)
0.14 VA (at 27.5 V operating voltage)
1,0 mA (at 27.5 V operating emergency operation voltage)
0.03 VA (at 27.5 V operating emergency operation voltage)
0 to 50 °C
10 to 75 % rel. humidity, moisture not permitted
(determined by MZ2 set up)
< 5 mA
< 5 mA
24 V; 50 mA
Vent module for 3 groups LM3G
17