15. ESPECIFICACIONES (1/2)
ONLINE - OPTIMA RT10 (UL)
Capacity / Capacidad
INPUT / ENTRADA
Input Voltage / Voltaje de Entrada
Input Range / Rango de Entrada
Frequency Range / Rango Frecuencia
Max. Current / Corriente Max.
Inrush Current / Corriente Pico max.
Phase / Fases
Power Factor / Factor de Potencia
THDi
Slew Rate / Seguimiento Frecuencia
OUTPUT / SALIDA
Model 230:
Model ISOTX:
Voltage Regulation / Regulación Salida
Frequency / Frecuencia (Batt. Mode)
Current Crest Ratio / Factor de Cresta
THDv
Dynamic Accuracy / Regulación Carga
Variable
Operating mode transient Response
Dynamic Load Transient Response
Recovery Time after Non-Linear Load Step
Transfer Times / Tiempos Transfer.
Waveform / Forma de Onda
DC offset / Componente DC en la salida
Power Outlets / Salidas
OVERLOAD / SOBRECARGA
AC Mode / Modo Normal
Battery Mode / Modo Batería
Bypass Mode / Modo Bypass
EFFICIENCY / EFICIENCIA @ (100%/75%/50%/25%) R LOAD
Eco Mode / Modo ECO
AC Mode / Modo AC
Battery Mode / Modo Batería
Inverter Efficiency / Eficiencia Inversor
BTU @ 100% LOAD
PROTECTIONS / PROTECCIONES
Surge / Contra Picos
Short Circuit / Cortos en la salida
Input Current / Corriente de Entrada
Starting Time / Tiempo de Arranque
www.xmart-ups.com
MANUAL DE USUARIO - OPTIMA RT10 6K/10K-UL
(RT10 6KVA-230)
6000VA / 6.000W
Rated Input / Entrada Nominal: 208/220/230/240 Vac (single phase: L-N-G)
Load 0-60% (L-L: 110V-300V) // (L-N: 63V-173V)
Load 61-80%: (L-L: 140V-300V) // (L-N: 80V-173V)
Load 81-100%: (L-L: 176V-300V) // (L-N: 101V-173V)
30A (RMS)
200A max.
1 Phase+Neutral+Ground / 1 Fase+Neutro+Tierra
<4% @ 100%load
1 phase (L-N): 208/220/230/240Vac
Dual Isolated Outputs: (L-N): 104/110/115/120Vac
50 Hz +/- 0.1 Hz / 60 Hz +/- 0.1 Hz (auto sense)
< 1% @ Linear Load / Carga Lineal
<4 @ No Linear Load / Carga no Lineal
<5% (load variations 20%-100% & 100%-20% R Load)
Comply to IEC 62040-3 (Class 1)
Comply to IEC 62040-3 (Class 1)
100ms ( IEC 62040-3, ref Non-linear load)
Terminal Block / Regleta de Conexión
100%~110%: 10min. / 110%~130%: 1min. / 130%~150% : 1s / >150% 20ms
100%~110%: 30s / 110%~130%: 10s / 130%~150% : 1s / >150% 20ms
100%~130%: only warning / >130% : 1min.
MODEL 230V: 99% / 99% / 98% / 97% - MODEL ISOTX: 95% / 95% / 94% / 93%
MODEL 230V: 94% / 93% / 87% / 83% - MODEL ISOTX: 90% / 89% / 83% / 80%
MODEL 230V: 92% / 91% / 85% / 81% - MODEL ISOTX: 88% / 87% / 82% / 81%
1228
All lines protection / Protección en todas las líneas (L-N, L-G, N-G): > 650J (10/1000us)
(Enable: Keeps output up to 4s / mantiene salida 4s (If/si V-out> 50V)
(Disabled: Current Limited 100ms then cut-off // Limita corriente 100ms luego corta salida)
Fuse protected / protegido por fusibles
VER.2008.14-One (ESP)
(RT10 10KVA-230)
10000VA / 10.000W
40 - 70 Hz
> 0.99 @ 100%load
/
< 6% @ 50%load
1 Hz / s
+/- 1%
3:1 @ 100% load.
0 ms
Sine Wave / Sinusoidal Pura
50 mV
97% Inverter (@ 100 LOAD)
7s - 10s (@ 100% load)