Descargar Imprimir esta página

LEGRAND Wattstopper LMRC-102 Guia De Inicio Rapido página 2

Publicidad

The LMRC‑102 communicates to all other DLM devices connected
to the DLM Local Network. Connection drawings are for example
only. The low voltage LMRJ cables can connect to any DLM device
with an open RJ45 receptacle.
All line voltage wiring is #12 AWG. Each relay is rated for up to
20A, total load for LMRC‑102 not to exceed 20A.
Plug n' Go supports the most energy efficient control strategy. For example, if at least
two loads, one switch and one occupancy sensor are connected to the DLM local
network, the system operates load A as Automatic ON, Automatic OFF and load B as
Manual‑On, Automatic‑Off.
See DLM device Quick Start Guides to determine how each device affects the PNG
operation of the LMRC‑102.
Load Control Arbitration
To take full advantage of automatic PnG configuration, review these simple rules about load control
arbitration.
After the room controllers are connected to the DLM Local Network and powered up they
automatically negotiate to determine which controller becomes the Master and the load numbers for
each relay on the DLM Local Network.
The Master is the controller with the most load relays. If more than one controller has the most
relays, the one with the highest serial number becomes the Master.
The LMRC‑102 has two load relays. In a DLM local network with only LMRC‑102 room controllers,
the LMRC‑102 with the highest serial number is the Master, carrying Load 1 and Load 2. The next
highest serial number would have Load 3 and Load 4, and so forth.
Load Selection Procedure
A configuration button (Config) allows access to our patented Push n' Learn™ technology to change binding
relationships between sensors, switches and loads.
Step 1 Enter Push n' Learn
Press and hold the Config button (on any DLM device) for 3 seconds.
The red LED on the LMRC‑102 begins to blink as does the red LED on ALL other communicating devices
connected to the DLM Local Network.
The red LEDs continue to blink until you exit PnL mode.
All loads in the room turn OFF immediately after entering PnL, then one load will turn ON. This is Load #1, which is bound to switch
button #1 and occupancy sensors as part of the Plug n' Go factory default setting.
All switch buttons and sensors that are bound to this load have their blue LED solid ON.
Step 2 Load selection
Press and release the Config button to step through the loads connected to the DLM Local Network. As each load turns ON note the
devices (switch buttons and sensors) that are showing a bright solid blue LED. These devices are currently bound to the load that is ON.
The blue LED on the room controller or plug load controller connected to the load is also lit.
• To unbind a switch button from a load, press the switch button while its blue LED is ON bright. The blue LED goes dim to indicate
the button no longer controls the load that is currently ON.
• To unbind an occupancy sensor, press the up () or down () adjustment button while its blue LED is ON. The blue LED turns
OFF to indicate the sensor no longer controls the load that is currently ON.
Pressing the switch or up () or down () button again while the load is ON rebinds the load to the button or sensor and the blue LED
illuminates brightly.
Step 3 Exit Push n' Learn
Press and hold the Config button until the red LED turns OFF, approximately 3 seconds.
PLUG N' GO OPERATION (PNG)
OPTIONAL UNIT ADJUSTMENT - PUSH N' LEARN (PNL)
CONNECTIVITY
Corner Mount
Sensor
Switch
Switch
2
Ceiling Mount
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
Line/Hot
Black wire
LMRC
102
Room
Controller
Daylight Sensor
J-Box
Load A ON/OFF button
Blue LED ON when load is ON
Serial
Number
0461373638
Master
0461373679
Line
Voltage
Neutral
White wire
Loads
1
2
Yellow wire
Red wire
to Load 2
to Load 1
Load B ON/OFF button
Room
Load
Controller
Control
LMRC-102
3
A
0341373638
4
B
LMRC-102
1
A
0341373638
2
B
Config button &
red LED

Publicidad

loading

Este manual también es adecuado para:

Wattstopper lmrc-102-u