Page 8.0
If a twin system is used (see Par. 6.3) on page 8.0
you can set one of the 3 possible twin operation
modes:
circulators alternate in regulation every 24
operating hours. If one of the 2 malfunctions, the
other takes over regulation.
work at the same time and at the same speed.
This mode is useful when a flow rate is required
that cannot be provided by a single pump.
performed by the same circulator (Main), the other
(Reserve) takes over only if there is a malfunction
of the Main one.
If the twin communication cable is disconnected
the systems automatically figure as Single,
working completely independent of each other.
Page 12.0
On page 12.0 you can set the operating mode of
the output relay:
1.
Indication of alarms present in the system.
2.
Indication
stopped/pump running.
Page 13.0
On page 13.0 you can set the system status in
ON, OFF or controlled by a remote signal EXT
(digital input IN1).
If ON is selected the pump is always on.
If OFF is selected the pump is always off.
If EXT is selected, reading of the status of digital
input IN1 is enabled. When input IN1 is energised
the system goes ON and the pump is started (on
the Home Page the messages "EXT" and "ON"
ENGLISH
Alternate every 24h: The 2
Simultaneous: The 2 circulators
Main/Reserve: Regulation is always
of
pump
status:
pump
-
14
appear alternately at bottom right); when input IN1
is not energised the system goes OFF and the
pump goes off (on the Home Page the messages
"EXT" and "OFF" appear alternately at bottom
right).
For the connection of the inputs see par. 5.1.1