6. Electrical work
6.1.1. Indoor unit power supplied from outdoor unit
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
A
* Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Indoor unit model
Minimum circuit ampacity
Maximum rating of overcurrent protective device
Indoor unit-Outdoor unit
Indoor unit earth
Wired remote controller-Indoor unit
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Wired remote controller-Indoor unit
*1. Max. 50 m, 165 ft
*2. Max. 500 m, 1640 ft (For two wired remote controllers: Max. 200 m, 656 ft)
*3. The figures are NOT always against the ground.
S3 terminal has 24 V DC against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.
3. Use wires rated 600V or more for the power supply cables and the indoor unit/outdoor unit connecting cables.
4. Install an earth longer than other cables.
6.2. Remote controller (Optional parts)
6.2.1. For wired remote controller
1) Two wired remote controllers setting
If two wired remote controllers are connected, set one to "Main" and the other to "Sub".
For setting procedures, refer to "Function selection of remote controller" in the operation manual for the indoor unit.
Note:
When connecting two remote controllers, be sure to use the same model of remote controller.
1 System
C
F
B
L1
L2
D
GR
S1
S1
S2
S2
S3
S3
E
1
G
2
PCA-A24,30
1A
*1
3 × AWG14 (polar)
*2
2 × AWG22 (Non-polar, unshielded)
*3
*3
*3
1:1 System
Outdoor unit power supply
Wiring circuit breaker or isolating switch
CN105
(RED)
Outdoor unit
Indoor unit/outdoor unit connecting cords
Wired remote controller (Optional parts)
H
Indoor unit
Indoor unit earth
Indoor controller board
PCA-A36, 42
2A
15A
1 × Min. AWG14
208/230 V AC
24 V DC
12 V DC
7