Assembly
4.5.1
General
CAUTION
Risk of cutting and injury!
Risk of cutting and injury due to production-related, sharp sheet metal edges on the unit.
•
Use personal protective equipment (cut-proof gloves).
•
Handle with care.
The following general requirements must be ensured for safe and reliable operation of the top filterfan:
•
Choose a switch cabinet installation site that provides for adequate ventilation of the system.
•
The top filterfan must always be assembled in a horizontal installation attitude.
•
Protect the assembly site against heavy contamination.
•
The ambient temperature must be below the permitted switch cabinet interior temperature.
•
Make sure that the seal is not damaged because otherwise the IP protection can no longer be guaranteed.
•
Keep the minimum distance between parts that form light arcs and the unit: 30.5 cm (12'') (UL508A sec. 22).
•
Installations in the switch cabinet must not obstruct air circulation.