Descargar Imprimir esta página

PowerWalker LiFe Battery System 48-100 Manual De Instrucciones página 11

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

2.3 Specifications
Model
Capacity
Battery Cell Technology
Battery Expansion
Nominal Voltage
Rated Capacity
Full Discharge Voltage
Max. Continuous
Discharge Current
Max. Discharge Current
Discharge Efficiency
Protection
Max. Charge Voltage
Max. Charge Current
Standard Charge Method
Inner Resistance
Battery Life Cycles
Dimension (D x W x H)
Dimension with stand feet
(D x W x H)
Net Weight (kg)
Operation Temperature
Storage Temperature
IP Protection
Communication
LiFe Battery System 48-100
Lithium Iron Phosphate
Up to 10 units
above 150 A requires the use of PDU
192 A at 1 min.
56 V ± 0.1 V
Max. 100 A; default 30 A
0.2C CC (Constant Current) charge to FC,
CV (Constant Voltage) charge till charge
current decline to <0.05C
8000 cycles: for 60% DOD at 1C
discharging current and 0.2C recharging
current with > 50% capacity.*
2000 cycles: for 90% DOD at 1C
discharging current and 0.2C recharging
current with >80% capacity.*
(*Compared to original capacity)
185 x 540 x 420 mm
185 x 540 x 530 mm
Charge/ Discharge: 0 ºC ~ 50 ºC
Optimum temperature: 10ºC ~ 35ºC for
best life cycles
-20ºC ~ 60 ºC;
20°C ± 5°C recommended
RS485 (RJ45), CAN extension port (RJ11)
8
5120 Wh
51.2 VDC
100 Ah
42 VDC
150 A;
90%
BMS
≤20mΩ
48
IP 20

Publicidad