Step 4: Please follow below steps to prepare battery cable with
supplied external battery connectors. The cable length should be
prepared based on the real distance between battery module and
inverter module.
The recommended cable size is listed as below:
Wire Size
1*4AWG
(a) Loosen and disassemble the plug of the supplied battery
connector.
(b) Insert the battery cable through the tunnel and housing, and
strip battery cable 11.5 ± 0.2mm.
(c) Crimp the cable and the plug with a proper crimping tool (ex.
hydraulic clamp) together into a hexagon shape as shown in
below chart. Then, move the housing toward plug and tighten
them.
Cable mm 2
25
22