Descargar Imprimir esta página

Defender DT-800Lan 'Turbo' Installacion Y Mantenimiento página 60

Publicidad

Idiomas disponibles

Idiomas disponibles

ETHERNET NETWORK CONNECTIVITY:
The DT-x00Lan series devices have been designed to be monitored and programmed remotely using the
DEFENDERTECH "DT-FogControl" and "DT-MultiFogControl" software.
DT-FogControl is responsible for programming:
The IP address, port,
Date and time
Setting the block time slot
Automatic Activation Timer, daily, weekly and for Negligence
Download the technical event log
Liquid Level Reset
Fault signal reset (Note: if the fault is persistent, the signal will continue)
Perform the "shot" (if there are the necessary technical conditions)
Changing the passwords of the 3 levels of access
The default IP address is 192.168.1.99 port 502.
DT-FogControl also allows you to check the status of the device and the wire inputs, as well as the basic
and special programming set physically through the DipSwitches.
DT-MultiFogControl is responsible for monitoring simultaneously the operating status of several Fogs
Generators (even in different geographical sites).
Both software can be requested for free by making a request (complete
IP ADDRESS AND PASSWORD RESET PROCEDURE
1. Disconnect ARM and FOG
2. Switch the appliance off completely
3. Note down the DIP-SWITCH configuration
4. Turn all DIP-SWITCH OFF
5. Remove the Jumper from BUZZ (J3)
6. Place the Jumper on J2
7. Set the DIP-SWITCH No. 10 to ON
8. Supply the appliance
9. Set the DIP-SWITCH no. 1 to ON
10. Switch the appliance off again
11. Remove the Jumper from J2 and replace it on BUZZ (J3)
12. Restore the DIP-SWITCH as noted down before (point 3)
13. Supply the appliance
Gateway and SubNet
with social data) at the following address
info@defendertech.eu
18

Publicidad

loading