SURFACE CONDUIT MOUNTING
NOTE: to avoid interference with components in the housing, use the most compact wire connectors appropriate to the wire gauge.
PREPARING THE UNIT FOR CONDUIT :
1
Remove the conduit plug from inside. The unit
is threaded to accept 1/2" NPT threads (14
TPI), which are common in rigid conduit and
EMT connector products. Rigid conduit or
EMT fittings can be directly threaded into the
housing without the need for a locknut, or for
wet locations, use an approved wet location
fitting.
Sized for ½" conduit
* A right angle screwdriver may be required to break
the plug from the paint
FINAL ASSEMBLY
Ensure all wires and
1
connectors are routed to
avoid interference with other
components. Line up the
Alignment pins (located at
diagonally opposite corners
of the front housing) with the
mating receptacles (two on
the rear housing).
SWITCH AIMING (FCT optics)
Note: Ships standard as WT option (wide throw mode)
1
Press and hold "Forward/Wide" button (Refer Page 5, Fig 1) for about 9 seconds to switch light beam aiming.
AFFINITY
INSTALLATION and WIRING
Conduit plug
To properly close the unit, it is
2
important to push the cover
straight onto the rear housing.
If the pins are not aligned with
the receptacles, the housing
will not close properly. Make
sure there are no gaps
between the front and rear
housings. If gap is present,
open the unit and reinstall the
front housing.
®
LIFE SAFETY SOLUTIONS
TEL: 800-705-SERV (7378)
techsupport-emergency@acuitybrands.com
BRANCH CIRCUIT WIRING :
2
The wiring compartment is sized for (3) incoming 12 AWG wires
and (3) outgoing 12 AWG wires and common wire connectors. If
your branch circuit is a larger AWG or you have a need for a
through-wire application, install the branch circuit raceway such
that you do not have to pass the circuit through the fixture.
Open
(Clockwise) *
Sheet metal
clip
Alignment pin
www.lithonia.com
Page 3
912-00021-002
Rev. CA, 2/2020
© 2020, Acuity Brand Lighting,Inc.
All Rights Reserved.