8.- NORMAS PARA MONTAJE EN RACK (max. 49 COFDM-QAM - 7 subracks de 7u. de altura - 8,7")
8.1.- Installation
of
the
ventilation facilities.
In order to facilitate the renewal and
circulation of the air inside the rack, thus
reducing the temperature of the COFDM-
QAM units and in consequence improving
its characteristics, it is advisable to place 2
ventilation units of 25W, particularly when
the rack with the COFDM-QAM is located in
warm place, with a temperature higher than
40°C.
Frontal
Subracks
fig. 1
These ventilators will be placed on a tray,
that is screwed onto the top part of the
Rack, fig. 1 and 2, and in this way the venti-
lators will be able to extract the air from the
rack
with
COFDM-QAM and will be able to expel it via
the gap (approx. 3-5 cm) at the top part of
the
Rack.
fig. 2
To mount the units in the rack with
ventilation, you must mount a blank plate
ref. 5173 between the modules to allow the
correct ventilation of the equipment, as also
ref. 5073 to supplement units, as in fig. 4.
fig. 3
48
COFDM QAM - TS PROC
TDT
TDT
TDT
TDT
TDT
5173
fig. 4