CLEARANCE TO COMBUSTIBLES
(Refer to Figures 4 and 5)
The following stated clearances represent the minimum
distances between the stove and any other object. No
objects should encroach into this space. This includes
but is not limited to carpet, furniture, children, pets,
clothing, fuel, or any other object. These clearances
may only be reduced by regulatory authority within
United States or Canada.
CAUTION: KEEP FURNISHINGS AND OTHER
COMBUSTIBLE MATERIALS AWAY FROM THE
HEATER.
KEEP THE AREA ADJACENT TO THE HEATER
FREE FROM ALL COMBUSTIBLE MATERIALS,
GASOLINE, AND OTHER FLAMMABLE
VAPORS.
The stove shall not be less than 29.5 inches (74.93 cm)
from a side wall and [U.S. - 1 1.5 inches (29.21 cm);
Canada - 16.5 inches (41.91 cm)] from the back wall.
The wall of a vertical vent pipe must not be less than
31 inches (78.74 cm) from a side wall and [U.S. - 13
inches (33.02 cm); Canada - 18 inches (45.7 cm)] from
the back wall.
The Minimum floor-to-ceiling distance of the room is
84 inches (213.4 cm).
The minimum distance between the ceiling and the
wall of any horizontal vent pipe is 18 inches (45.7 cm).
31"
(78.74 cm)
29.25"
(74.93 cm)
Single Burn Rate Wood Fire Stove
FIGURE 4
84"
(213.4 cm)
Floor
Protector
CORNER INSTALLATION (Refer to Figure 6)
The stove shall not be less than [U.S. - 15 inches (38.1
cm); Canada - 16 inches (40.6 cm)] from a corner. The
wall of a vertical vent pipe must not be less than [U.S.
- 17 inches (43.18 cm); Canada - 18 inches (45.7 cm)]
from any corner.
U.S. - 17" (43.18 cm)
Canada - 18" (45.7 cm)
U.S. -
15"
16"
(38.1 cm)
(407 mm)
Canada -
16"
(40.6 cm)
Floor Protector
FIGURE 6
FLOORING SPACE (Refer to Figure 7)
In Canada, to comply with CSA B365, Installation Code
for Solid-Fuel-Burning Appliances and Equipment, any
combustible covering beneath the appliance and/or
within the area extending horizontally at least 18 inches
(45.7 cm) beyond the appliance on any side equipped
with a door, and at least 8 inches (20.3 cm) beyond
E6
Operating Instructions and Owner's Manual
18" (45.7 cm)
U.S. - 13"/ 33.02 cm
(Backwall Exit)/
1 1"/27.94 cm (Ceiling Exit)
Canada - 18" (45.7 cm)
U.S. - 1 1.5"/ 29.21 cm
(Backwall Exit)/
9.5"/ 24.13 cm (Ceiling Exit)
Canada - 16.5" (41.91 cm)
FIGURE 5
U.S. - 15" (38.1 cm)
16"
Canada - 16" (40.6 cm)
(407 mm)