INPUT A
GND
INPUT B
GND
Note: Channel A and channel B have a common
ground!
3.3. Mounting (retrofit) PDC with ex-works
installed ZENNER pulser to corresponding
ZENNER water meters
Please refer to the relevant installation instructions
of the pulser and take the PDC as described in
section 3.4 in operation.
3.4. Commissioning PDC
A) PDC wireless M-Bus: The commissioning is
performed via the optical interface.
The parameters to be programmed using a laptop
with the ZENNER MSS Configurator license, the
universal interface MinoConnectRadio with
Bluetooth interface and the associated special
ZENNER infrared optical head IrCombiHead.
Alternatively, the use of an Android handhelds
with a MeterReaderLight license instead of a
laptop is possible. Activation takes place auto-
matically when the PDC module has received
more than 10 pulses from the meter.
B) The LoRaWAN® PDC module is to be activated and
parameterised by means of the ZENNER infrared
opto head IrCombiHead. Here, an additional
activation by means of illumination (at least 8
seconds) of the IR diodes is possible.
Upon successful activation, the device sends a join
request to the server and waits for acceptance (join
accept).
If no connection is made then a further request is
sent every minute (to a max. of 5 requests). The
indicator light (red LED) indicates the status of the
connection process:
rapid flashing: No reply yet received
■
slow flashing: Successful connection
■
If no successful join is achieved then the device will
send a random join request every day until a
successful connection is made (LED does not display
later attempts to join).
+
+
Fig. 1 Connection sketch PDC
Abb.:
Anschlussschema PDC
To configure at least:
serial number of meter connected to the PDC
■
module
Initial value = present value of the register of the
■
connected meter
Pulse value of the connected meter
■
The respective transmission interval is preset.
■
(Interval can be configured by using MSS-Soft-
ware or ZENNER Device Manager app)
Additional settable parameters:
Reset warnings
■
Setting due date
■
4. Wall mounting
Install wall bracket with the enclosed wall plugs and
screws as shown below on a flat wall surface. Slide
PDC over the wall bracket to the PDC clicks.
Dismounting of the PDC from the wall bracket: Use
screwdriver or similar tool to push the upper strap
of the wall bracket backwards and then pull the
PDC downwards.
Dimensions (LxWxH):
127mm x 40,6mm x 42mm
Data telegram contents (wM-Bus)
The PDC module can be delivered
with various data telegrams:
Telegram content
Current value
Current date
Due date values
Current monthly value
Another 11 monthly values
Status information 1
Status information 2
* Data telegram according DIN EN 13757-4.
** wM-Bus, manufacturer specific data telegram
Typ A*
Typ B*
Typ C**
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
9