FUNZIONAMENTO
Offset
Descrizione
140
Configurazione sistema
141
Stato Operativo
Tº ambiente esterna
142
(Outdoor ambient temperature)
Tº di ingresso dell'acqua
143
(Water Inlet unit temperature)
Tº di uscita dell'acqua
144
(Water outlet unit temperature)
145
H-Link Communication State
146
Software PCB
103
PMML0351A rev.4 - 04/2020
Valori
Lettura/Scrittura
b0: Zone 1 Heating
Available
b1: Zone 2 Heating
Available
b2: Zone 1 Cooling
Available
b3: Zone 2 Cooling
Available
b4: DHWT Available
b5: SWP Available
b6: Room thermostat
available Zone 1
b7: Room thermostat
available Zone 2
b8: Wireless Setting C1
b9: Wireless Setting C2
b10: Wireless Room
Temperature C1
b11: Wireless Room
Temperature C2
b12: Slave Unit
0: OFF
1: Cool Demand –OFF
2: Cool Thermo-OFF
3: Cool Thermo-ON
4: Heat Demand-OFF
5: Heat Thermo-OFF
6: Heat Thermo-ON
7: DHW-OFF
8: DHW-ON
9: SWP-OFF
10: SWP-ON
11: Alarm
-80~100
-80~100
-80~100
0: No alarm
1: There is no
communication with
RCS or Yutaki unit
during more than 180
seconds
2: Data initialization
Disponibilità
VRF
Lettura
Lettura
Lettura
Lettura
Lettura
Lettura
Lettura
RAC
ATW
O
O
O
O
O
O
O